By A.J. Keilty, President, KEILTY Realty Management

In an Ontario rental, the landlord tests the smoke alarms, not the tenant. Ontario's Fire Code requires a test annually and after every change in tenancy. It also requires one after a battery is replaced, and after any change to the circuit a hard-wired alarm is connected to.
That is four triggers, and only one of them is on a calendar. The other three are events an owner who lives two hours away may not hear about. This post sets out what the Fire Code requires, how you get into the unit, and what you have to write down. It also covers what changes when you hand the job to a property manager, and what does not.
It is yours. The Fire Code is O. Reg. 213/07, made under the Fire Protection and Prevention Act, 1997. Its general rule, Article 1.2.1.1 of Division A, is: "Unless otherwise specified, the owner is responsible for carrying out the provisions of this Code."
For smoke alarm maintenance and testing, Article 6.3.3.2 of Division B narrows that: in the case of a rental suite, "only the landlord shall be considered to be the owner ..." for that purpose.
The same article defines the landlord as the person, firm or corporation that owns the rental unit. The definition adds "including an agent acting on their behalf for purposes of carrying out duties under this Subsection ..." and says the term "... does not include the tenant." So a lease clause that tells the tenant to test the alarms does not move the Fire Code duty. The tenant has duties of their own, covered below, but testing is not one of them.
Article 6.3.3.8 applies to rental suites and sets out the schedule:
Sentence (2) says annually and does not set a date, so the Fire Code does not tie the annual test to a lease anniversary or a season. Pick a fixed month for each property and keep it.
The change-in-tenancy test is the one owners miss. The simplest time to do it is between one tenant leaving and the next one moving in. While the unit is empty, you have no tenant to give notice to.
The battery and circuit triggers are the hard ones to track, because they happen when you are not there. An electrician who works on the circuit your hard-wired alarms are connected to, during a panel upgrade for example, has changed that circuit. Sentence (4) wants a test after that work.
Sentence 6.3.3.8 (5) defines the test: smoke alarms "... shall be tested by activating the smoke alarm test feature." That is the button on the alarm. Where the Building Code requires a visual signalling component, Sentence (6) requires that the test also activates it.
A failed test is not the end of the job. Division B Article 1.1.1.2 (3) reads: "Any appliance, device or component of a device that does not operate or appear to operate as intended when checked, inspected or tested as required by this Code shall be repaired or replaced if the failure or malfunctioning of the appliance, device or component would adversely affect fire or life safety."
A smoke alarm that stays silent meets that description. Article 6.3.3.3 (1) adds the direct duty: "Smoke alarms shall be maintained in operating condition."
Age matters too. Article 6.3.3.7 (1) says "A smoke alarm shall be replaced within the time frame indicated in the manufacturer’s instructions." An alarm that passes its button test can still be past its replacement date, so read the date stamp on the back while you are there. Sentence (2) then sets the minimum standard for the replacement. That standard turns on whether the suite falls under the retrofit rules and when it was built.
Yes. Division B Article 1.1.2.1 (1) opens: "If this Code requires tests and corrective measures or operational procedures to be carried out, records shall be made noting what was done and the date and time it was done."
Sentence (3) says the records "... shall be retained at the building premises for examination by the Chief Fire Official." Sentence (4) deems electronic records that can be made readily available on request to comply.
Article 1.1.2.2 (1) sets the retention period. Keep each record at least two years after it is prepared. Keep enough that the latest record of each test, and the one before it, are on file. For a single-family rental, an entry for each test noting the date and time, which alarm, the result and what you replaced does the job. Keep it at the property, or electronically where you can produce it promptly on request.
The record is also your best evidence, after a fire, that the alarm worked when it was last tested.
That depends on the building. Section 2.13 of Division B sets the installation rule for suites of residential occupancy. Article 2.13.2.1 (1) requires a smoke alarm in the hallway serving a sleeping area, or between the sleeping area and the rest of the unit if there is no hallway. It also requires one on each storey without a sleeping area.
But Section 2.13 has two switches at the top. Sentence 2.13.1.1 (2) says the Section "... does not apply to buildings that are subject to Part 9." Part 9 is the retrofit part. Sentence (3) says it does not apply where smoke alarms were installed under the Building Code as it read on or after April 6, 1998.
A detached house with one dwelling unit and no other major occupancy is outside Part 9 entirely, under Article 9.1.2.2 (1).
A house with two units is where Part 9 can bite. Article 9.1.2.2 (2) still takes it out of Part 9 if the building already satisfies the applicable fire safety requirements of the Building Code. Section 9.8 covers a detached, semi-detached or row house with two residential units. It must be three storeys or less and no larger than 600 square metres in building area. One unit must sit at least partly above the other, or the two must share an interior means of escape.
There, Article 9.8.4.2 (4) requires "At least one smoke alarm shall be installed on each storey of a residential unit." Sentence (5) drops that requirement where interconnected alarms are installed under Article 9.8.4.1, which call for one on each storey anyway.
Interconnected, hard-wired alarms come in under Section 9.8 only on certain routes. Sentence 9.8.2.2 (2) allows a 15-minute fire separation instead of 30 minutes if the units have interconnected smoke alarms. Sentence 9.8.3.3 (2) requires them where a shared means of escape serves a unit entirely on the third storey. Clause 9.8.3.4 (1) (b) requires them where a window is relied on as the second means of escape.
If you do not know which route your duplex was built or retrofitted on, find out before you replace anything.
Article 6.3.3.4 reads: "The landlord of each rental suite shall give the tenant a copy of the smoke alarm manufacturer’s maintenance instructions or approved alternative maintenance instructions." Put the copy in the move-in package and keep proof you delivered it.
The tenant's side is Article 6.3.3.5. A tenant "... shall notify the landlord as soon as the tenant becomes aware that ..." a smoke alarm in the unit is disconnected, not operating, or impaired. Article 6.3.3.6 adds: "No person shall disable a smoke alarm." That one binds everyone, tenant included.
Those two articles are the tenant's duties. They do not shift the testing schedule. If a tenant tells you an alarm chirps, that report is your trigger to go and fix it. If you replace the battery, Sentence 6.3.3.8 (3) requires a test after it.
With written notice. Under section 27 (1) of the Residential Tenancies Act, 2006, a landlord may enter "in accordance with written notice given to the tenant at least 24 hours before the time of entry ..." for the listed reasons.
Paragraph 1 reads: "To carry out a repair or replacement or do work in the rental unit." Paragraph 4 covers an inspection to determine whether the unit complies with "health, safety, housing and maintenance standards ..." if the inspection is reasonable. Our reading is that an annual alarm test fits paragraph 4, and replacing a dead alarm fits paragraph 1.
Section 27 (3) says the notice "... shall specify the reason for entry, the day of entry and a time of entry between the hours of 8 a.m. and 8 p.m." Keep the window tight. Our post on when a landlord can enter without permission covers the Divisional Court decision that rejected a nine-hour window for an annual smoke alarm inspection.
A worked example. You want to test the alarms in a Kingston semi on Wednesday, 2027-03-10, between 10 a.m. and noon. If you hand the notice to the tenant in person under section 191 (1) (a), it has to reach them by 10 a.m. on Tuesday, 2027-03-09.
If you mail it, section 191 (3) deems it given "... on the fifth day after mailing." A deemed day carries no time of day, so leave a clear day. Mail it no later than Wednesday, 2027-03-03, for deemed delivery on Monday, 2027-03-08. The 24-hour rule counts hours, not business days.
Not on our reading. The Fire Code definition says the landlord is the owner "including an agent acting on their behalf for purposes of carrying out duties under this Subsection ..." The word is "including": it adds the agent rather than substituting one. A manager acting for you becomes a landlord for these purposes alongside you. Nothing in Article 6.3.3.2 takes you out. That is our reading of the definition rather than something the Code states in so many words.
What a manager changes is whether the four triggers get caught. That means the annual test on the property calendar and the turnover test built into the move-out inspection. It means every battery swap and electrical job logged against the unit so the follow-up test happens. And it means each result filed with the date and time Article 1.1.2.1 asks for. That is the system KEILTY Realty Management runs for the owners we manage for.
Missing a required test is a contravention of the regulations. Clause 28 (1) (c) of the Fire Protection and Prevention Act, 1997 makes contravening the regulations an offence, subject to subsection (2), which concerns only Part IX.
Under section 28 (3), an individual convicted of an offence under subsection (1) faces "... a fine of not more than $50,000 for a first offence and not more than $100,000 for a subsequent offence, or to imprisonment for a term of not more than one year, or to both." Under section 28 (4), a corporation faces up to $500,000 for a first offence and $1,500,000 for a subsequent one.
Section 28 (5) reaches a director or officer who knows the corporation is violating or has violated the fire code.
Section 30.2, in force 2026-01-01, also allows administrative penalties by order for a contravention of a prescribed provision. The caps are $10,000 for an individual and $100,000 for anyone else, or a lesser prescribed amount. Which provisions are prescribed for that purpose is set by regulation, so do not assume every Fire Code article is.
Section 30.1 limits prosecutions to one year after the facts come to the knowledge of a local firefighter or the responsible assistant to the Fire Marshal. That clock runs from knowledge, not from the missed test.
If an inspector finds the gap and makes an order, our post on how to challenge a fire safety order sets out the route and the deadlines.
Yes. Article 6.3.4.8 (2) requires the landlord of a rental suite of residential occupancy to test carbon monoxide alarms "annually and after every change in tenancy or after every change of residents ..." It also requires a test after a battery is replaced, and after any change to the circuit of a connected alarm. Sentence (3) uses the same test: activate the test feature.
If the property has carbon monoxide alarms, run both tests on the same visit and record both.
For a rental in Kingston or anywhere else in Eastern Ontario, four standing items cover the Fire Code side:
If you own one house, that is four lines in a calendar. If you own a duplex in Kingston and a semi in Belleville, it is at least eight, plus the triggers you will only hear about after the fact. That is the point at which owners hand the schedule to a manager. Our single-family rental management page sets out what we take on.
Can I make my tenant responsible for testing the smoke alarms? No. Article 6.3.3.2 of the Fire Code makes only the landlord the owner for smoke alarm maintenance and testing in a rental suite. Its definition of landlord does not include the tenant. The tenant must report a disconnected, non-working or impaired alarm under Article 6.3.3.5 and must not disable one, but the testing duty under Article 6.3.3.8 stays with you.
How often does an Ontario landlord have to test smoke alarms? Annually and after every change in tenancy, under Article 6.3.3.8 of the Fire Code. Add a test after replacing the battery in a battery-operated alarm, and after any change to the circuit of a hard-wired one. The test is done by activating the alarm's test feature. A record of the date, time and what was done must be kept for at least two years.
Does hiring a property manager make the manager responsible instead of me? On our reading, it adds the manager rather than replacing you. The Fire Code defines the landlord as the owner, including an agent acting on the owner's behalf for these duties, so both can be responsible. What a manager adds is the system that catches every trigger and keeps the records.
Smoke alarm testing is a small job with four triggers, and only one of them arrives on a calendar. If you would rather not track the other three yourself, we can.
Own a rental in Kingston or Eastern Ontario? KEILTY Realty Management manages it for a flat monthly rate. Get a free rental evaluation or book a 30-minute discovery call with A.J. Keilty.
This post is general information about Ontario residential tenancy law as of 2026-11-20, not legal advice. Legislation, regulations and tribunal practice change. For advice on a specific property or situation, speak with a lawyer or licensed paralegal.